Before installation, carefully check whether the chiller equipment is damaged, and then choose a suitable place. the
2. The place to install the chiller unit is the floor, installation pad or foundation, and it can bear the weight of the whole equipment. the
3. The chiller should be placed in the machine room with a room temperature of 4-40 degrees, and there should be enough space around the unit for future maintenance and management. the
4. One end of the chiller should have a space for cleaning the condenser tube bundle, which cannot be occupied by other equipment in the workshop. the
5. Select the appropriate water pipe diameter, which can withstand the pressure of the cooling system when the chiller is running at high power, and connect it correctly. 6. For common application scenarios, the water flow velocity through the condenser is between 1.0-3.6m/s, and the water flow should be stable under any load conditions. the
7. Pipeline design and installation are carried out according to conventional methods. The chilled water pump is connected to the water inlet pipe of the chiller to ensure the positive pressure and flow in the unit, and maintain a certain shock absorption effect to prevent the water in the evaporator from being drained due to the shutdown of the water pump. . the
8. The fixing of the pipeline and the unit should be separated, and the hanger cannot be fixed at the same time. Avoid stress exerted on the components of the chiller. the
9. Analyze and deal with the water quality of the evaporator and condenser cooling water. If the water quality is poor, the structural materials of the large fouling system should be selected to reduce the water quality fouling, sedimentation, corrosion, etc. that affect the heat exchange of the system, reduce the performance of the unit, and increase the operation and maintenance costs. the
10. Install cooling water filter, clean and maintain regularly to improve water quality. the
11. After the leak test of the industrial chiller equipment is completed, the connection port should be treated with anti-rust treatment.







