A Solution For A Steel Processing Factory

The processing workshop for metal materials such as steel and steel pipes covers an area of 15,000 square meters, is 8 meters high, has 170 workers, and is equipped with 10 heavy-duty metal processing machines. The outdoor maximum temperature remains at 35℃ for 3 to 4 months each year. How many kilowatts of cooling capacity is needed?
To estimate the cooling capacity (in kilowatts, kW) needed for a metal material processing workshop of the described size and usage, we'll account for space volume, heat sources (people, machines), ambient conditions, and ventilation.
1.Workshop Basic Information

Item Value
Area 15,000 m²
Height 8 m
Volume 15,000 m² × 8 m = 120,000 m³
Number of workers 170
Heavy machines 10 units
Outdoor max temperature 35°C (3–4 months/year)
Target indoor temperature ~26–28°C
Structure Steel/metal or concrete structure (likely with poor insulation)
Ventilation Assume 5–10% fresh air exchange

2.Cooling Load Estimation

Cooling load consists of:

1) Heat gain from the building envelope (walls, roof, windows): Poorly insulated metal buildings at 35°C ambient can contribute significantly

Estimated: 500–700 kW

2) Fresh air ventilation cooling load (5–10% new air): For 5% fresh air on 120,000 m³, ≈ 6,000 m³/h of hot air needs cooling

Estimated: 120–180 kW

3) People heat load: 170 workers × 150 W = 25.5 kW

4) Machinery heat load: 10 heavy-duty metal machines, assume 10–15 kW of heat per unit

Total: 100–150 kW

5) Lighting & miscellaneous: Estimated: 50–80 kW

6) Safety margin (10–15%): Adds around 100–150 kW

3.Total Estimated Cooling Capacity

Total cooling capacity required ≈ 900 to 1,300 kW
Depending on insulation, new air ratio, and indoor air distribution system.

4.Recommended Cooling Capacity

To ensure comfortable working conditions during peak heat months, allowing some buffer:

Recommended: 1,100 ~ 1,300 kW of cooling capacity
5.Cooling System Type Suggestion

Type Details
Air-cooled chiller + AHU/FCU Best for large open factories, scalable
Rooftop package AC units If roof load is acceptable, easy to install
Direct expansion (DX) multi-split systems Not recommended for large industrial workshops