< img height="1" width="1" style="display:none" src="https://www.facebook.com/tr?id=967547061139808&ev=PageView&noscript=1" />
andyzhu@shzhongyou.com    +86-180-0189-6115
Cont

Have any Questions?

+86-180-0189-6115

Rooftop Package Units

Rooftop Package Units

This roof-mounted air conditioner has constant temperature and humidity functions. It is suitable for roofs with large spaces. It is mainly air-cooled. A variety of air return and return methods are optional. It is small in size and full-featured. You can choose the "temperature" according to customer needs. The "wet accuracy" range is as follows:

PERFORMANCE:
Only Cooling
Cooling Capacity Range: 12.9kW - 490.5kW
Temperature Range: 18~32℃, Accuracy Range: ±2.0℃
Air Flow Range: 3000 m3/h to 73000 m3 /h
Refrigerant: R22/R407C
Support OEM/ODM Service
Brand:Feizhong
Send Inquiry

Product Introduction Technical Parameter

 

Our Rooftop Package Units

Feizhong air conditioners can be placed on rooftops or outdoor open spaces, eliminating the need for a machine room and saving investment. The rooftop ac unit does not require secondary refrigerant and the system efficiency is high. The unit has full functions, which can conveniently achieve air purification, dehumidification, humidification, cooling, heating, fresh air volume regulation and other functions.
Rooftop Package Units

 

Product Features

 

1: Wide Scope Of  Application: This series of products includes constant temperature and humidity, cooling and heating (cooling only), heat pump and other varieties. The constant temperature and humidity type unit can meet the requirements of high temperature and humidity places, and the cooling and heating (cooling only) type unit can meet the comfort requirements. , the heat pump type unit can be used for two purposes, saving heating operation costs.

2: Save Investment: Feizhong commercial rooftop ac unit is Installed on the roof or outdoor open space, without the need for a machine room, saving space. The best rooftop ac unit does not require water pumps, cooling towers, fan coils and other supporting equipment, save initial investment.

3. Easy Installation: Many commercial rtu hvac do not need to be equipped with refrigerant pipes and cooling water pipes on site. They are equipped with air ducts and connected to the power supply, and they are ready for use, saving on-site construction time and costs.

4. Reasonable Structure: The top plate of all units adopts a unique structure to ensure that water does not enter the unit. The door panels are made of polyurethane foam to ensure heat insulation performance. The electrical box adopts a sealed structure to ensure the safety of electrical appliances. The power wiring is placed in the electrical box. No worries of roof leaks.

5: Operational Safety: All commercial hvac rooftop units are equipped with high-voltage, low-voltage, overload, short-circuit, phase failure, overheating, lack of wind pressure and other protections, as well as fire valve chain protection.

6: Control Intelligence: All commercial rooftop hvac unit adopt advanced control instruments. The instruments can be equipped with two-hand operators and are placed in outdoor units and indoor control rooms. They are very convenient to use and operate. The instrument is equipped with RS485 interface for remote control.

7: Convenient Function Expansion: Many roof top hvac units are equipped with a variety of functional sections, which can easily realize functions such as air cooling, dehumidification, heating, humidification, filtration, and fresh air ventilation. Function sections can also be added according to user customization.

A123

 

Applications

 

Feizhong roof air conditioners are suitable not only for shopping mall, restaurant, entertainment, office building, clubs, and general industrial workshop, but also for clean places in industrial workshop such as medicine, food, electronics, chemicals, scientific research, and machinery.

 

11111111

 

WHY US

RoofTop Air Conditioner 2

30 workers are responsible for product assembly

Guarantee factory production capacity and ensure timely delivery

RoofTop Air Conditioner 6

20 skilled workers are responsible for welding and other processes

Exquisite craftsmanship, production of high-quality equipment

RoofTop Air Conditioner 1

10 Technician focuses on product development and design

Innovation and customization, providing more professional solutions, and only making products suitable for users.

RoofTop Air Conditioner

5 Workers Are Responsible for after-sales

Parts replacement and maintenance to ensure efficient operation of equipment

Send Inquiry

We have an advanced technical team and a professional after-sales department that can provide 24-hrs online consulting services.

We warmly welcome you to wholesale customized chiller made in China here from our factory.

Pls contact us for more details.

Hot Tags: rooftop package units, China rooftop package units manufacturers, suppliers, factory, best commercial rooftop hvac units, air con on roof, roof top aircon, roof unit, roof top hvac units, rooftop central air conditioner

Performance Model

WKLF

013

WKLF

028

WKLF

060

WKLF

070

WKLF

090

WKLF

120

WKLF

140

WKLF

180

WKLF
210

WKLF

240

WKLF

280

WKLF

310

WKLF

350

WKLF

380

WKLF

430

WKLF

490

Cooling Capacity kW 12.9 27.6 60.5 70.8 89.9 121 141.6 181.5 212.4 239.7 281.5 308.9 351.6 382.3 431.9 490.5
104kcal/h 11.1 23.7 52.0 60.9 77.3 104.1 121.8 156.1 182.7 206.1 242.1 265.7 302.4 328.8 371.4 421.8
Energy Regulation % 0,100 0,50,100 0,33,66,100 0,25,50,75,100
Air Volume m3/h 3000 6000 10000 12000 15000 20000 24000 30000 36000 40000 48000 52000 56000 62000 68000 73000
External Static Pressure Pa ≥250 ≥250 ≥300 ≥300 ≥400 ≥500 ≥500 ≥550 ≥600 ≥600 ≥650 ≥650 ≥700 ≥700 ≥800 ≥800
Temperature Range And Accuracy Temperature Control Range 18 ~32℃,Accuracy±2.0℃
Power   380V,50Hz,3-phase 5-wire system
Rated Power kW 5.4 9.8 22.1 26.2 33.7 45.5 55.4 71.5 81.6 99.9 109.9 121.7 143 156.6 185.6 198.6
Compressor Type Fully Enclosed Scroll Type Semi-Enclosed Screw Type
QTY 1 1 2 2 2 4 4 4 6 1 1 1 1 1 2 2
Nominal Input Power
kW
4.05 7.5 17.6 20 26 35 40 52 60 74.8 82.4 90.7 104 114.6 136.6 149.6
Refrigerant Type R22/R407C
Throttling Mode Thermal Expansion Valve
Evaporator Type Aluminum Finned Copper Tube
Fan Type Double Inlet Centrifugal Fan
Power kW 0.8 1.5 3 4 5.5 7.5 11 15 15 18.5 18.5 22 30 30 37 37
Condensate Fan Type Low Noise Axial Flow Type
QTY 1 2 2 2 2 4 4 6 6 6 6 6 6 8 8 8
Power kW 0.55 0.8 1.5 2.2 2.2 3 4.4 4.5 6.6 6.6 9 9 9 12 12 12
Air Filter Type Plate Initial Effect
Dimensions L*W*H mm Can Be Customized According To Customer Requirements
Weight kg 450 750 1500 1580 1750 2550 2750 3750 4050 4850 5750 5800 6050 7100 7350 7650

 

 

 

Noted Unit Nominal Operating Conditions
Indoor side Outdoor side
Dry bulb temperature Wet bulb temperature Dry bulb temperature Dry bulb temperature
27℃ 19℃ 35℃ 36℃
Specifications and parameters are subject to product improvement or update without prior notice.

Send Inquiry