< img height="1" width="1" style="display:none" src="https://www.facebook.com/tr?id=967547061139808&ev=PageView&noscript=1" />
frank@shzhongyou.com    +86-180-0189-6115
Cont

Have any Questions?

+86-180-0189-6115

video

Water Cooled Constant Temperature And Humidity Air Conditioner

Water-cooled constant temperature and humidity air conditioner is a special air conditioner with high precision that integrates dehumidification, humidification, heating, and cooling. It needs frozen water source. It is composed of a fully enclosed scroll compressor, a copper tube jacketed aluminum fin evaporator, a thermal expansion valve and a shell and tube condenser! All stainless steel condensate pan and bottom water pan, electrostatically sprayed sheet metal shell.

Cooling Capacity Range: 7.9kW - 150kW
Temperature Range: 18~28℃, Accuracy Range: ±0.5~1.0℃
Humidity Range: 50~70%RH, Accuracy Range: ±5~10%RH
Air Flow Range: 1500 m3/h to 28000 m3/h
Refrigerant:R22/R410A
Support OEM/ODM Service
Brand: Feizhong

Application Fields:
Precision machinery, electronics, optical equipment, surface treatment, medical and health care, biopharmaceuticals, food processing, fine chemicals, power distribution rooms, various measurement and testing laboratories, etc.
Send Inquiry

Product Introduction Technical Parameter

 

 

Water Cooled Constant Temperature And Humidity Air Conditioner Features

1.Water-cooled air conditioning comfort temperature humidity system' conditions for measuring cooling capacity:

Inlet air dry bulb temperature 23°C, wet bulb temperature 17°C; cooling water inlet temperature 30°C, outlet water temperature 35°C.

2. Evaporation Coil: direct expansion evaporator, the copper tube is a high heat conduction seamless copper tube with a hydrophilic punched aluminum sheet, the aluminum sheet is tightly attached to the copper tube and the tube is mechanically expanded to make the copper tube and the aluminum sheet tightly fit.

3. Condenser: Water-cooled shell-and-tube condenser. The shell is made of copper plate with a thickness of 6mm or more. After anti-rust treatment, the pressure resistance is 400PSI. The two ends of the tube side are sealed with flanges. The end cover is made of cast iron. .

4. The constant temperature and humidity air conditioning adopts the forward-curved multi-blade centrifugal suction impeller.

The impeller must pass the dynamic balance test. The long-term operation still has low noise and small vibration, and can maintain high-efficiency air supply. It adopts self-calibrating ball bearings .

5. Reasonable refrigeration cycle, easy maintenance.

Considering the different needs of different users and the convenience of maintenance, we have designed a single cycle circuit, that is, one compressor and one refrigeration cycle. When a certain refrigerating cycle is repaired due to failure, the other refrigerating cycles can operate as usual.

6. Safe and reliable operation, excellent and stable performance.

To prevent abnormal situations, the unit is equipped with safety protection devices: high-voltage switch, over-six overload protection device, relays, etc., are all made of high-quality foreign products to ensure greater efficiency.

7. Micro-computer control technology, multi-functional automatic control.

Water-cooled hvac temperature and humidity control adopts the combination of microcomputer and high-level display screen to monitor the unit in all directions, automatic safety control, and use fuzzy control principle to precisely adjust energy, so as to truly realize the safe and economical operation of the unit.

 

Working Principle

 

Constant temperature and humidity air-conditioning system is composed of refrigeration system, heating system, control system, humidity system, air circulation system, and sensor system. The above systems are divided into two aspects: electrical and mechanical refrigeration. The working principle and working process of several main systems are described below.

The operation of the constant humidity and humidity machine system is through three interrelated systems: refrigerant circulation system, air circulation system, and electrical automatic control system;

1
2

Refrigerant Circulation System

 

The liquid refrigerant in the evaporator absorbs the heat of the air (the air is cooled and dehumidified) and starts to evaporate. Finally, a certain temperature difference is formed between the refrigerant and the air, and the liquid refrigerant is completely evaporated into a gaseous state, and then sucked by the compressor. And compressed (increased pressure and temperature), the gaseous refrigerant absorbs heat through the condenser (air-cooled/water-cooled), and condenses into a liquid. After throttling through the expansion valve (or capillary tube), it becomes a low-temperature and low-pressure refrigerant and enters the evaporator to complete the refrigerant cycle process.

Air Circulation System

 

The fan is responsible for inhaling air from the air return port. The air passes through the evaporator (cooling, dehumidification), humidifier, heater (heating), and then is sent to the space required by the user through the air supply port. The air sent out is mixed with the air in the space and returned to the room. to the return air outlet.

3
1 5

 

Electrical Automatic Control System

Including power part and automatic control part.

The power supply part supplies power to compressors, fans, humidifiers, etc. through contactors.

The automatic control part is further divided into temperature, humidity control and fault protection parts:

The temperature and humidity control is through the temperature and humidity controller, which compares the temperature and humidity of the return air with the temperature and humidity set by the user, and automatically operates the compressor (cooling, dehumidification), humidifier, electric heating (heating) and other components to achieve Automatic control of constant temperature and humidity.

Fault protection control is achieved through the combination of pressure protection, delayer, relay, overload protection, etc., to control the failure protection of compressors, fans, humidifiers and other components.

 

Send Inquiry

We have an advanced technical team and a professional after-sales department that can provide 24-hrs online consulting services.

We warmly welcome you to wholesale customized chiller made in China here from our factory.

Pls contact us for more details.

Hot Tags: Water Cooled Constant Temperature And Humidity Air Conditioner, China Water Cooled Constant Temperature And Humidity Air Conditioner manufacturers, suppliers, factory, constant temperature and humidity air-conditioning system, air conditioning comfort temperature humidity model, comfort temperature and humidity, constant temperature and humidity air conditioner, Temperature and humidity control in air conditioning system, constant temperature and humidity air conditioning system

Model Performance

H8

H10

H15

H22

H30

H34

H45

H60

H70

H90

H105

H115

H135

H150

Air Conditioning Unit Performance

Cooling Capacity

kW

7.9

9.8

14.5

21.6

29.5

34.2

44.5

59.5

70

89.5

104.1

114.6

134.8

150

104 kcal/h

0.68

0.84

1.25

1.86

2.54

2.94

3.83

5.12

6.02

7.70

8.95

9.86

11.59

12.90

Energy Regulation

%

100, 0

100, 50, 0

Heating Capacity

Electric Heating

kW

5

5

6

9

12

15

21

27

36

45

46

48

60

66

104 kcal/h

0.43

0.43

0.52

0.77

1.03

1.29

1.81

2.32

3.1

3.87

3.96

4.13

5.16

5.68

Hot Water Heating

kW

8

10

16

19

22

30

46

50

62

67

80

85

90

95

104 kcal/h

0.69

0.86

1.38

1.63

1.89

2.58

3.96

4.3

5.33

5.76

6.88

7.31

7.74

8.17

Steam Heating

kW

10

10

21

26

30

40

62

68

83

90

105

115

120

132

104 kcal/h

0.86

0.86

1.81

2.24

2.58

3.44

5.33

5.85

7.14

7.74

9.03

9.89

10.32

11.35

Air Volume

m3/h

1500

2200

3000

4300

6000

7000

8000

10000

13000

17000

19000

21000

22000

28000

External Static Pressure

Pa

150 [0]

150 [0]

150 [0]

≥250 [0]

≥280 [0]

≥350 [0]

≥300 [0]

≥300 [0]

≥330 [0]

≥350

≥400

≥400

≥400

≥400

Unit Noise

dB (A)

60 [56]

62 [59]

64 [60]

66 [64]

69 [65]

69 [65]

69 [66]

71 [67]

71 [67]

73

76

76

79

80

Temperature Range And Accuracy

℃

Temperature control range 18 ~ 28 ℃, accuracy ± 0.5 ~ 1.0 ℃

Humidity Control Range And Accuracy

% RH

Humidity control range 50~70%, accuracy ±5~10%

Power Supply

 

380V, 50Hz, 3-phase 5-wire system

Total Capacity Of The Unit

kW

10.5 [10.45]

10.97 [10.9]

13.6 [13.17]

19 [18.6]

23 [22.2]

28.95 [27.85]

39.75 [37.85]

50.15 [47.35]

68.2 [66.8]

83.15

88.75

95.75

115.25

132

Compressor

Type

Fully enclosed vortex type

Quantity

1

2

Nominal Input Power kW

2.25

2.6

3.8

5.9

6.5

8

12

15

18

22.4

27

30

37.5

41.3

Cooling System

Refrigerant

Type

R22/R410A

Throttling Mode

Thermal Expansion Valve

Evaporator

Type

Copper tube with aluminum fin type

Condenser

The Form

Shell tube type

Water Amount t/h

1.77

2.19

3.24

4.83

6.60

7.65

9.95

13.30

15.65

20.01

23.28

25.62

30.14

33.54

Inlet/Outlet Pipe Diameter DN

DN32

DN40

DN50

DN65

DN80

Fan System

Fan

Type

Low noise centrifugal type with outer rotor

Quantity

1

2

Power kW

0.25 [0.2]

0.37 [0.3]

0.8 [0.37]

1.1 [0.5]

1.5 [0.7]

2.2 [1.1]

3 [1.1]

4.4 [1.6]

4.4 [3.0]

6

6

8

8

15

Air Filter

Type

Initial Effect

Heater

Electric Heating

Type

Electric Heat Type/PTC

Power kW

5

5

6

9

12

15

21

27

36

45

46

48

60

66

Hot Water Heating

Heating Capacity kW

8

10

16

19

22

30

46

50

62

67

80

85

90

95

Inlet/Outlet Pipe Diameter DN

25

32

Steam Heating

Heating Capacity kW

10

10

21

26

30

40

62

68

83

90

105

115

120

132

Inlet/Outlet Pipe Diameter DN

25

32

Humidifier

Type

Electrode Type

Humidification kg/h

4

5

13

Power kW

3

3.75

9.75

Inlet Pipe Diameter

1/2'

Dimensions

L mm

960

1260

1720

2000

2000

2300

2700

W mm

780

940

1050

1500

1800

2100

2200

H mm

1660 [2000]

1810 [2150]

1955 [2295]

1950

2050

2000

2140

Weight

kg

290

300

330

440

460

510

690

720

950

1000

1200

1500

1550

1900

Send Inquiry